EVP
- Application
Water supply: Pressure boosting for main pipes and high-rise buildings
Industrial pressure boosting:Water system,cleaning system,high pressure
washing system and firefighting system
Pressure boosting for pressure tank, sprinkling irrigation and trichling irrigation
ir conditioner, cooling system and industrial cleaning - Features
Economic vertical multistage pumps
Applicable for a wide scope of different temperatures,flow rates and pressure ranges
Water inlet and outlet can be rotated for proper assembly in accordance with
installation requirement
Easy installation and maintenance
Advanced hydraulic model design,featuring stable operation and high efficiency
Cast iron water inlet and outlet with special anti-rust treatment
High-strength engineering plastic flow passage components
Reliable stainless steel welded shaft - Working Conditions
Liquid temperature:+ 5℃~60℃
Maximum ambient temperature:+ 40℃
Maximum pressure: 15 bar
Altitude:up to 1000 m
- Description
- Technical Data
- Dimensions
- Materials Table
- Ambient & Liquid Temperature
Description
Show Details
Download
Model | Power(P2) | Q(m3/h) | 0 | 1 | 2 | 3 | 4 | ||
Single-phase | Three-phase | kW | HP | Q(l/min) | 0 | 16.7 | 33.3 | 50 | 66.7 |
EVPm2-6 | EVP2-6 | 1 | 1.5 | H (m) |
69 | 65 | 52 | 37 | 18 |
EVPm2-7 | EVP2-7 | 1.1 | 1.5 | 82 | 75 | 62 | 45 | 25 | |
EVPm2-9 | EVP2-9 | 1.5 | 2 | 105 | 98 | 82 | 60 | 35 | |
EVPm2-11 | EVP2-11 | 1.8 | 2.5 | 130 | 119 | 98 | 69 | 37 |
Model | Power(P2) | Q(m³/h) | 0 | 1 | 2 | 3 | 4 | 5 | 6 | ||
Single-phase | Three-phase | kW | HP | Q(m3/h) | 0 | 16.7 | 33.3 | 50 | 66.7 | 83.3 | 100 |
EVPm4-6 | EVP4-6 | 1.5 | 2 | H (m) |
74 | 72 | 69 | 66 | 57 | 47 | 36 |
- | EVP4-8 | 2.2 | 3 | 98 | 95 | 92 | 86 | 76 | 63 | 47 |
Model | Power (P2) | Q(m3/h) | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | ||
Single-phase | Three-phase | kW | HP | Q(l/min) | 0 | 16.7 | 33.3 | 50 | 66.7 | 83.3 | 100 | 116.7 | 133.3 | 150 | 166.7 |
- | EVP6-7 | 3 | 4 | 68 | 67 | 66.5 | 65 | 63.5 | 62 | 60 | 58 | 56 | 54 | 51 |
Model | Power (P2) | Q(m³/h) | 0 | 1 | 2 | 3 | 4.5 | 6 | 7.5 | 9 | 10.5 | ||
Single-phase | Three-phase | kW | HP | Q(l/min) | 0 | 16.7 | 33.3 | 50 | 75 | 100 | 125 | 150 | 175 |
EVPm6H-5 | EVP6H-5 | 1.8 | 2.5 | H (m) |
64 | 62 | 60 | 58 | 54 | 47 | 38 | 28 | 16 |
- | EVP6H-8 | 3 | 4 | 103 | 100 | 97 | 95 | 90 | 80 | 66 | 50 | 31 |
Model | Power(P2) | Q(m³/h) | 0 | 2 | 4 | 6 | 8 | 10 | 12 | 14 | 16 | ||
Single-phase | Three-phase | kW | HP | Q(l/min) | 0 | 33 | 67 | 100 | 133 | 167 | 200 | 233 | 267 |
- | EVP10H-3 | 3 | 4 | H (m) |
56 | 55 | 54 | 52 | 49 | 46 | 42 | 39 | 29 |
- | EVP10H-4 | 4 | 5.5 | 75 | 74 | 72 | 70 | 67 | 64 | 60 | 53 | 43 | |
- | EVP10H-6 | 5.5 | 7.5 | 113 | 110 | 107 | 104 | 100 | 96 | 87 | 78 | 68 | |
- | EVP10H-8 | 7.5 | 10 | 150 | 147 | 143 | 139 | 134 | 127 | 120 | 108 | 92 |
Model | Power (P2) | A | B | C | D | E | F | G | H | |
Single-phase | Three-phase | kW | ||||||||
EVPm2-6 | EVP2-6 | 1 | 478 | 218 | 193 | 110 | 202 | 114.5 | G1 | G1 |
EVPm2-7 | EVP2-7 | 1.1 | 545 | 248.5 | 210 | 125 | 202 | 114.5 | G1 | G1 |
EVPm2-9 | EVP2-9 | 1.5 | 593 | 296.5 | 210 | 125 | 202 | 114.5 | G1 | G1 |
EVPm2-11 | EVP2-11 | 1.8 | 641 | 344.5 | 210 | 125 | 202 | 114.5 | G1 | G1 |
Model | Power (P2) | A | B | C | D | E | F | G | H | |
Single-phase | Three-phase | kW | ||||||||
EVPm4-6 | EVP4-6 | 1.5 | 521 | 224.5 | 210 | 125 | 202 | 114.5 | G1 | G1 |
- | EVP4-8 | 2.2 | 569 | 272.5 | 210 | 125 | 202 | 114.5 | G1 | G1 |
Model | Power (P2) | A | B | C | D | E | F | |
Single-phase | Three-phase | kW | ||||||
- | EVP6-7 | 3 | 686 | 337 | 221 | 134 | G1¼ | G1¼ |
Model | Power (P2) | A | B | C | D | E | F | G | H | |
Single-phase | Three-phase | kW | ||||||||
EVPm6H-5 | EVP6H-5 | 1.8 | 510 | 212.5 | 210 | 125 | 202 | 114.5 | G1¼ | G1½ |
- | EVP6H-8 | 3 | 655 | 297.5 | 240 | 141 | 218 | 121.5 | G1¼ | G1½ |
Model | Power (P2) | A | B | C | D | E | F | G | H | |
Single-phase | Three-phase | kW | ||||||||
- | EVP10H-3 | 3 | 554.5 | 187 | 240 | 141 | 227 | 127 | G1¼ | G1½ |
- | EVP10H-4 | 4 | 577.5 | 220 | 240 | 141 | 227 | 127 | G1¼ | G1½ |
- | EVP10H-6 | 5.5 | 680 | 286 | 262 | 152 | 244 | 135 | G1¼ | G1½ |
- | EVP10H-8 | 7.5 | 746 | 352 | 262 | 152 | 244 | 135 | G1¼ | G1½ |
No. | Part | Material |
1 | Fan cover | 08F |
2 | Fan | PP |
3 | Rear cover | Cast iron |
4 | Bearing | |
5 | Stator | |
6 | Rotor | |
7 | Gasket | Rubber |
8 | Flange | Cast iron |
9 | Motor bracket | Aluminum |
10 | Mechanical seal | |
11 | Pump barrel | AISI 304 |
12 | Impeller | Plastic |
13 | Diffuser | Plastic |
14 | Last stage diffuser | Plastic |
15 | Capacitor box | Plastic |
Max. Ambient temperature: +40°C
Liquid temperature: +5°C - 60°C